500kV变电站主变中性点接地方式及接地导体的选择应用
曾勇1, 杨永健2
1. 中国能源建设集团广东省电力设计研究院有限公司,广州 510663;
2. 广东电网有限责任公司中山供电局,广东 中山 528400
Application of Grounding Mode and Grounding Conductor for Power Transformer Neutral Point in 500kV Hub Substation
Zeng Yong1, Yang Yongjian2
1. Guangdong Electric Power Design Institute Co., Ltd, China Energy Engineering Group, Guangzhou 510663;
2. Zhongshan Power Supply Bureau of Guangdong Power Grid Company, Zhongshan, Guangdong 528400
全文: PDF (241 KB)   HTML (0 KB) 
输出: BibTeX | EndNote (RIS)      
摘要 本文总结了500kV电力变压器中性点的接地要求,分析了500kV主变中性点接地方式的选择,阐述了500kV主变中性点在主变或电网发生交流短路情况下采用直接接地或经小电抗接地的接地方式运行特点,在发生主变直流偏磁时迅速切换至经隔直装置接地方式运行特点,并基于上述中性点接地方式运行的特点,提出关于中性点接地导体选择的计算方法,最后结合工程对其选择应用的进行说明。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
曾勇
杨永健
关键词 直接接地小电抗接地隔直装置接地主变中性点接地导体    
Abstract:The grounding requirements of neutral point of 500kV power transformer are summarized in the paper. According to different characteristics of grounding mode and grounding conductor for power transformer neutral point in 500kV power transformer, the grounding mode works by solidly grounding or low-reactance grounding in AC short circuit conditions of main transformer or the gird, and quickly switch to DC-blocking device grounding in main transformer DC bias. Based on the characteristics of the neutral grounding operation mode, calculate grounding conductor for neutral point of power transformer, finally illustrate the selection and application in a project.
Key wordssolidly grounding    low-reactance grounding    DC-blocking device grounding    grounding conductor for neutral point of power transformer   