电气技术  2017, Vol. 18 Issue (9): 72-74    DOI:
技术与应用 |
一起220kV架空输电线路双伞型瓷绝缘子炸裂故障分析
夏令志1, 程登峰1, 秦金飞1, 李森林1, 季坤2
1. 国网安徽省电力公司电力科学研究院,合肥 230022;
2. 国网安徽省电力公司,合肥 230061
The Analysis on a Burst Fault of Double Umbrella Type Porcelain Insulators on a 220kV Overhead Transmission Line
Xia Lingzhi1, Cheng Dengfeng1, Qin Jinfei1, Li Senlin1, Ji Kun2
1. State Grid Anhui Electric Power Research Institute, Hefei 230022;
2. Sate Grid Anhui Electric Power Company, Hefei 230061
全文: PDF (252 KB)   HTML (1 KB) 
输出: BibTeX | EndNote (RIS)      
摘要 本文针对某220kV架空输电线路双伞型瓷绝缘子炸裂故障事件,抽取故障批次绝缘子进行试验分析,主要试验项目包括温度循环试验、工频击穿耐受试验、机电破坏负荷试验和孔隙性试验。结果显示该批次绝缘子3只样品中有2只机电破坏负荷试验不合格,实测机电破坏负荷值远低于额定值,破坏形式均表现为瓷件断裂,表明绝缘子质量存在问题。建议对该批次绝缘子进行更换,加强瓷绝缘子的入网、施工验收检测,并定期开展零值检测工作,及时更换零值、低值绝缘子。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
夏令志
程登峰
秦金飞
李森林
季坤
关键词 输电线路瓷绝缘子绝缘子炸裂机电破坏负荷试验    
Abstract:String the burst fault of double umbrella type porcelain insulators on a 220kV overhead transmission line, defective batch insulators were extracted for test analysis. The main test items included temperature cycle test, power frequency breakdown test, electromechanical failing load test and porosity test. The results showed that there were two electromechanical failing load tests in the three samples. The measured damage values of the electromechanical failure were much lower than the rated value. The failure modes were porcelain faults, indicating that there were problems with the quality of the insulator. It was recommended to replace the batch insulators, and strengthen the porcelain insulator testing in network, construction acceptance. The zero value detection work should be regularly carried out, and the low value and zero value insulators should be timely replaced.
Key wordstransmission line    porcelain insulator    insulator burst    electromechanical failing load test   
     出版日期: 2017-09-20
作者简介: 夏令志(1987-),男,安徽省安庆市人,硕士,工程师,主要从事高电压技术研究和输电线路运维工作。
引用本文:   
夏令志, 程登峰, 秦金飞, 李森林, 季坤. 一起220kV架空输电线路双伞型瓷绝缘子炸裂故障分析[J]. 电气技术, 2017, 18(9): 72-74. Xia Lingzhi, Cheng Dengfeng, Qin Jinfei, Li Senlin, Ji Kun. The Analysis on a Burst Fault of Double Umbrella Type Porcelain Insulators on a 220kV Overhead Transmission Line. Electrical Engineering, 2017, 18(9): 72-74.
链接本文:  
https://dqjs.cesmedia.cn/CN/Y2017/V18/I9/72