电气技术  2020, Vol. 21 Issue (10): 88-92    DOI:
电气设备检修与故障诊断 |
中性点不接地配电系统并联铁磁谐振状态频域解析方法
韩国强1, 刘相龙1, 赵一龙2, 仉志华2, 邹兵3
1.山东胜利通海集团东营天蓝节能科技有限公司,山东 东营 257200;
2.中国石油大学(华东)新能源学院,山东 青岛 266580;
3.中国石化股份胜利油田分公司运行管理中心,山东 东营 257000
Frequency domain analytical method for parallel ferroresonance state of distribution system with neutral point ungrounded
Han Guoqiang1, Liu Xianglong1, ZhaoYilong2, Zhang Zhihua2, Zou Bing3
1. Shandong Shengli Tonghai Group Dongying Tianlan Energy Saving Technology Co., Ltd, Dongying, Shandong 257200;
2. College of New Energy, China University of Petroleum (East China), Qingdao, Shandong 266580;
3. Operation Management Center of Shengli Oilfield Branch of Sinopec Corp., Dongying, Shandong 257000
全文: PDF (7074 KB)   HTML (1 KB) 
输出: BibTeX | EndNote (RIS)      
摘要 近年来,配电网大范围使用电缆代替架空线路,对地分布电容增大使得系统远超参数谐振区域,但当单相接地尤其间歇性弧光接地故障消失时,电压互感器饱和后引发的铁磁谐振现象时有发生。本文基于中性点不接地中压配电系统并联等效模型,利用描述函数法计算谐振时的线路参数状态,分析了电流与磁链间关系和非线性方程之间的规律,利用增量法求出其谐振状态条件下解的稳定性判据,构建了中性点不接地中压配电系统并联铁磁谐振状态频域解析方法,为分析配电网铁磁谐振频率分布提供了理论依据。仿真结果证明了该方法的有效性。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
韩国强
刘相龙
赵一龙
仉志华
邹兵
关键词 配电网中性点不接地系统铁磁谐振状态解析描述函数法    
Abstract:In recent years, cables have been widely used instead of overhead lines in the distribution network, and the increase of the distributed capacitance to the ground makes the system far beyond the parametric resonance region. However, when the single-phase grounding fault, especially the intermittent arc grounding fault, disappears, the ferroresonance phenomenon caused by PT saturation occurs from time to time. Non-ground neutral medium voltage power distribution system is based on the parallel equivalent model, using the describing function method to calculate the resonant state of the line parameters, analyzes the relationship between electric current and magnetic flux and the laws between the nonlinear equations. The incremental method is used to find out the resonance state under the condition of the stability criterion of solution, non-ground neutral medium voltage power distribution system is constructed in parallel ferro-resonance state frequency domain analysis method, to analysis provides theory basis for ferromagnetic resonance frequency distribution of the distribution network. Simulation results show the effectiveness of this method.
Key wordsdistribution network    ungrounded neutral system    ferroresonance    state analysis    descriptive function method   
收稿日期: 2020-03-08     
基金资助:国家自然科学基金面上项目(51977220); 山东省自然科学基金面上项目(ZR2019MEE057); 中央高校基本科研业务费专项资金资助项目(18CX05025A)
作者简介: 韩国强(1985-),山东省德州市人,本科,工程师,主要从事油田电气节能设备的研发与推广工作。
引用本文:   
韩国强, 刘相龙, 赵一龙, 仉志华, 邹兵. 中性点不接地配电系统并联铁磁谐振状态频域解析方法[J]. 电气技术, 2020, 21(10): 88-92. Han Guoqiang, Liu Xianglong, ZhaoYilong, Zhang Zhihua, Zou Bing. Frequency domain analytical method for parallel ferroresonance state of distribution system with neutral point ungrounded. Electrical Engineering, 2020, 21(10): 88-92.
链接本文:  