电气技术  2021, Vol. 22 Issue (10): 84-87    DOI:
电气设备检修与故障诊断 |
备自投闭锁功能完善及试验分析
孙大根
国能大渡河瀑布沟水力发电总厂,四川 雅安 625304
Function improvement and experimental analysis of the back-up-switchover-unit
SUN Dagen
CHN Energy Daduhe Pubugou Hydropower General Plant, Yaan, Sichuan 625304
全文: PDF (774 KB)   HTML (1 KB) 
输出: BibTeX | EndNote (RIS)      
摘要 备自投即备用电源自动投入装置,能在工作电源故障或其他原因断开后迅速地自动将备用电源投入工作,但如果工作电源因负荷端短路等原因造成电源跳闸,则应由电源端保护装置跳闸信号闭锁备自投装置动作,否则备用电源会合于故障回路,造成二次破坏。本文结合现场试验,提出了某电站400V配电系统备自投装置闭锁功能的实现方法,以提高备自投装置运行的可靠性。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
孙大根
关键词 备自投闭锁试验分析    
Abstract:The back-up-switchover-unit can put the standby power supply into operation quickly after the working power supply is disconnected due to fault or other reasons. However, if the working power supply trips due to short circuit at the load end, the tripping signal of the power supply protection device shall block the action of the back-up-switchover-unit, otherwise the standby power supply will also be closed in the fault and lead to secondary damage. Based on the field test, this paper analyzes the problems existing in the locking function of the back-up-switchover-unit, and puts forward the corresponding solutions, which improves the reliability of the back-up-switchover-unit.
Key wordsthe back-up-switchover-unit    the locking function    test    analysis   
收稿日期: 2021-04-27     
作者简介: 孙大根(1986—),男,安徽桐城人,本科,工程师,主要从事水电站电气专业管理工作。
引用本文:   
孙大根. 备自投闭锁功能完善及试验分析[J]. 电气技术, 2021, 22(10): 84-87. SUN Dagen. Function improvement and experimental analysis of the back-up-switchover-unit. Electrical Engineering, 2021, 22(10): 84-87.