Abstract:In this paper, the operation characteristics of power transformers under DC bias are studied and analyzed. Firstly, based on the basic principle of transformer vibration and magnetic bias, the vibration mechanism and basic characteristics of transformer under DC magnetic bias are analyzed. Then, combined with the noise monitoring data of two 220kV transformers in a new substation, the DC bias mechanism of power transformer is analyzed and the spectrum characteristics are extracted. The analysis results verify the basic characteristics of transformer vibration and noise under the magnetic bias mechanism. Finally, this paper puts forward some suggestions for improvement.
柳林, 尤方圆, 余汪洋, 杨勇, 王军. 电力变压器直流偏磁振动噪声特征研究[J]. 电气技术, 2019, 20(7): 9-12.
Liu Lin, You Fangyuan, Yu Wangyang, Yang Yong, Wang Jun. The study of characteristics of the transformer vibration noise under DC magnetic bias. Electrical Engineering, 2019, 20(7): 9-12.