Analysis of Generator Tripping Caused by Excitation System Over Excitation Limit |
Yang Qi |
Shanxi Zhangshan Electric Power Co., Ltd , Changzhi, Shanxi 046021 |
|
|
Abstract This paper analyzed the generator tripping event during excitation limit and protection dynamic checking process of EX2100 excitation systems, and obtained the cause of the accident was the wrong increasing magnetic operation when over excitation limit action . Because the two sets of controller parameters inconsistent resulted in the excitation system trip. This paper gave some suggestions for excitation system dynamic checking test.
|
Published: 28 September 2015
|
|
|
|
[1] GE. EX2100 Excitation Control User’s Guide[M]. Revised 101027, USA: General Electric Company, 2010. [2] 王清明. 300 MW机组励磁低励限制引起功率异常波动分析[J]. 热力发电, 2009, 38(12): 75-77. [3] 竺士章, 陈新琪. 励磁系统的过励限制和过励保护[J]. 电力系统自动化, 2010, 34(5): 112-115. [4] 吴笃贵. 静止励磁系统保护配置方案[J]. 电力系统自动化, 2005, 29(19): 72-75, 99. [5] 杨斌, 王劲松. 一起PT初级熔丝故障导致停机的事故分析[J]. 电力安全技术, 2008, 10(5): 37-38. |
|
|
|