Fault analysis of 500kV HGIS disconnecting switch's insulating tension pole
YU Xiaoxiang
State Grid Fujian Electric Power Co., Ltd, Maintenance Branch, Fuzhou 350001

Download: PDF (5827 KB)   HTML (1 KB) 
Export: BibTeX | EndNote (RIS)      
Abstract  Through the analysis of disintegration a tripping fault of the 500kV hybrid gas insulated switchgear, confirmed the cause of fault is due to internal defects of disconnecting switch's insulating tension pole. The internal defects gradually deteriorated in the operating process, and the flashover happened. Then in process of reclosing, thebreakdown products and shielded cap of moving contact dropped on the level basin insulation, it caused the flashover of insulator, later the isolator broke down. In all these cases, we put forward recommendations to improve device reliability.
Key wordshybrid gas insulated switchgear (HGIS)      disconnecting switch      insulating tension pole      surface flashover     