Electrical Engineering  2023, Vol. 24 Issue (3): 73-76    DOI:
Technology & Application Current Issue| Next Issue| Archive| Adv Search |
Analysis and suggestions on open line test of converter station
YAN Kaige, LIU Tao, AI Songbo, ZHAN Tianle
EHV Branch of State Grid Jiangxi Electric Power Co., Ltd, Nanchang 330000

Download: PDF (963 KB)   HTML (1 KB) 
Export: BibTeX | EndNote (RIS)      
Abstract  This paper introduces the function and principle of DC transmission open line test, and studies the influence of trigger angle and resistance-capacitance parameter on open line voltage. Because the open line test voltage protection configured by the DC system is based on the ideal model calculation, which is quite different from the measured voltage, it is not actually put into operation. In this paper, a strategy to replace the old voltage protection is proposed, the resistance-capacitance value is calculated according to the measured voltage to predict whether the test can succeed, and avoid further reducing the triggering angle to cause breakdown and equipment damage.
Key wordsopen line test      trigger angle      resistance-capacitance parameters      protection     
Received: 29 December 2022     
Service
E-mail this article
Add to my bookshelf
Add to citation manager
E-mail Alert
RSS
Articles by authors
YAN Kaige
LIU Tao
AI Songbo
ZHAN Tianle
Cite this article:   
YAN Kaige,LIU Tao,AI Songbo等. Analysis and suggestions on open line test of converter station[J]. Electrical Engineering, 2023, 24(3): 73-76.