| Analysis of a discharge fault in a 500 kV gas-insulated transmission line conduit gallery |
| LIANG Xuri |
| State Grid Jibei Electric Power Co., Ltd. Ultra High Voltage Branch, Beijing 102488 |
|
|
|
|
Abstract Regarding a discharge fault in the 500 kV gas-insulated transmission line (GIL) conduit gallery of a certain ultra-high voltage substation, an SF6 component test is conducted on the GIL corridor gas chambers to identify the faulty chamber firstly. Then, by inspecting the interior of the GIL corridor and performing a disassembly analysis of the triple-column insulators, the discharge process is ascertained. Subsequently, foreign matter in the gas chamber is collected and its components are analyzed, thereby determining the composition of the foreign matter and its possible source location. Finally, by hypothesizing and verifying possible locations of the foreign matter that could have caused the discharge, the exact source of the foreign matter is pinpointed, thereby proposing corresponding corrective and preventive measures, which is beneficial for improving the operational reliability of similar GIL corridors.
|
|
Received: 08 January 2026
|
|
|
|
| Cite this article: |
|
LIANG Xuri. Analysis of a discharge fault in a 500 kV gas-insulated transmission line conduit gallery[J]. Electrical Engineering, 2026, 27(7): 79-84.
|
|
|
|
| URL: |
|
https://dqjs.cesmedia.cn/EN/Y2026/V27/I7/79
|
[1] 周国伟, 董建新, 肖珊珊, 等. 高压断路器弹簧操动机构典型故障应力分析[J]. 浙江电力, 2018, 37(12): 93-99. [2] 麻秀范, 冯晓瑜. 考虑5G网络用电需求及可靠性的变电站双Q规划法[J]. 电工技术学报, 2023, 38(11): 2962-2976. [3] 梁旭日, 麻震烁, 李冰玉, 等. 一起500kV液压弹簧机构断路器油压低分合闸闭锁故障原因分析[J]. 电气技术, 2022, 23(9): 93-96. [4] 程槐号, 陈滔. 基于大口径安装手孔的气体绝缘金属封闭开关设备扩建新方法[J]. 电气技术, 2019, 20(11): 88-92, 96. [5] 孙大根. 500kV断路器防跳试验方法优化[J]. 电气技术, 2022, 23(5): 95-97, 104. [6] 汪建成, 谢文刚, 宫瑞磊, 等. 550kV GIL三支柱绝缘子设计[J]. 高压电器, 2018, 54(5): 114-118. [7] 肖登明, 阎究敦. 气体绝缘输电线路(GIL)的应用及发展[J]. 高电压技术, 2017, 43(3): 699-707. [8] 关为民, 卞超, 谭婷月, 等. 苏通GIL综合管廊SF6气体泄漏分布特性数值模拟研究[J]. 高压电器, 2020, 56(11): 102-110. [9] 胡智莹, 耿秋钰, 魏来, 等. 直流GIS/GIL中驱赶电极与微粒陷阱的协同抑制作用及优化设计方法[J]. 电工技术学报, 2023, 38(12): 3338-3349. [10] 费烨, 刘云鹏, 陈江波, 等. 特高压GIL壳体温升测试分析及工程运维措施建议[J]. 高压电器, 2020, 56(12): 292-296. [11] 黎卫国, 张长虹, 杨旭, 等. GIL三支柱绝缘子表面电荷积聚特性[J]. 高压电器, 2025, 61(1): 189-196. [12] 徐爱华, 臧春艳, 李一硕, 等. 基于声振联合定位技术的GIL机械故障检测系统研究[J]. 高压电器, 2025, 61(6): 52-58, 67. [13] 刘鹏, 吴泽华, 朱思佳, 等. 缺陷对交流1100kV GIL三支柱绝缘子电场分布影响的仿真[J]. 电工技术学报, 2022, 37(2): 469-478. [14] 杜伯学, 董佳楠, 梁虎成. 特高压GIL非均匀热气流特性与三支柱绝缘子绝缘裕度分析[J]. 电工技术学报, 2023, 38(6): 1678-1686. [15] 黎卫国, 张长虹, 杨旭, 等. 换流站GIL设备关键部件故障分析[J]. 高压电器, 2020, 56(11): 251-258. [16] Q/CSG1206007—2017 电力设备检修试验规程[S]. |
|
|
|