Datang Lubei Power Analysis on Zero Sequence Protection Misoperation and Secondary Wiring Analysis in Plant Auxiliary Power System with 6kV Voltage Level
Wang Maosong, Ge Zhaozhong, Li Zhanwang
Datang Lubei Power Plant, Binzhou, Shandong 251909
Abstract:This paper analyses zero sequence protection misoperation of Datang Lubei power plant and offers some anti-interference measures. Meanwhile, in order to avoid misoperation or refusing to move of the relay protection device, it analyses the zero sequence current transformer series-parallel of the secondary connection, when the motors are supplied with more than two cables through more than two above zero sequence current transformer.