Analysis of One Bus Insulation Fell Fault in DC System |
Dong Sheng Chen Wentong Zheng Xiaodong Liu Songcheng Gao Yin |
Jinhua Electric Power Company Substation Maintenance Room, Jinhua, Zhejiang 321000 |
|
|
Abstract DC system grounding, will cause the protection tripping or malfunction; this paper explores the causes of DC system grounding fault and introduces the harm, and summarizes the most domestic substation DC system insulation detection method. Combined with a 220kV substation DC system insulation decreased with accident, reason of insulation produced by voltage change characteristic, that is because of branch Ⅱ DC bus insulation drop caused by power supply, and is mainly composed of capacitor, inductor and other components of the recorder, the DC bus voltage to the ground lead anode fall.
|
Received: 20 April 2015
Published: 23 March 2015
|
|
|
|
Cite this article: |
Dong Sheng Chen Wentong Zheng Xiaodong Liu Songcheng Gao Yin. Analysis of One Bus Insulation Fell Fault in DC System[J]. Electrical Engineering, 2015, 16(03): 97-99.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2015/V16/I03/97
|
[1] 张毅, 张泉, 李永丽. 直流系统接地检测[J] .电力系统及其自动化学报, 2005, 17(1): 27-30. [2] 李冬辉, 徐津津. 一种新的直流系统环网接地故障检测方法[J]. 电网技术, 2006,30(2): 57-60. [3] 李冬辉, 贾巍. 直流系统环网接地故障检测方法[J].中国电力, 2006, 39(2): 5-9. [4] 陈韬, 胡书琴. 变电站直流系统接地故障的分析及对策[J]. 电力学报, 2009, 24(2): 145-147. [5] 赖志刚, 毛鹏, 杨杰. 一起直流接地事件的分析及改造[J]. 电力系统保护与控制, 2009, 37(12): 106-108. |
|
|
|