Influence of Solar Irradiation on Power Transformer Hot-spot Temperature Calculation |
Xue Fei Chen Jiong |
School of Electrical Engineering, Shanghai University of Electric Power, Shanghai 200090 |
|
|
Abstract In environment with a high ambient temperature and strong solar irradiation, transformer winding hot-spot temperature may increase over its maximum permissible limit, it does not only threaten the safe operation of transformer, but will largely reduce the transformer insulation life. Therefore, it is important to take research of the impact of the sun on the power transformer thermal behavior. In this paper, a model for calculating solar irradiation power is presented to account for the effect on transformer, and it has been transformed as a heating source when calculating transformer hot-spot temperature. A simple modification of IEEE loading guide model is preformed, the comparison between before and after shows that the influence of solar irradiation on transformer hot-spot calculation and daily operation cannot be neglected.
|
Published: 20 April 2015
|
|
|
|
[1] 陈伟根, 赵涛, 江淘莎, 等. 改进的变压器绕组热点温度估算方法[J]. 高压电器, 2009, 45(1): 53-56. [2] IEC 60076-7 Power transformers-Part 7. Loading guide for oil-immersed power transformers[Z]. 2005. [3] Schlabbach J. Improvement of permissible loading of transformers by solar shield[J]. EUROCON, Computer as a Tool, IEEE Region 8, 2003(2): 305-309. [4] Goswami D Y, Kreith F, Kreider J F. Principles of Solar Engineering, Second Edition, Taylor and Francis, 2000: 26-34. [5] 陈伟根, 苏小平, 陈曦, 等. 变压器顶层油温预测热模型影响因素分析及其改进[J]. 高电压技术, 2011, 37(6): 1329-1335. [6] 温波, 刘爽, 冯加奇, 等. 油浸式电力变压器绕组温度场的二维仿真分析[J]. 变压器, 2009, 46(9): 35-38. |
|
|
|