The Cause and Solution of Low Watching Voltage of Siemens 100% Stator Ground Fault Protection with 20Hz Voltage Injection |
Chen Fenghua1, Wu Hao2, Gao Dijun3 |
1. Power Generation Company Huizhou Pumped Storage Power Station, Huizhou, Guangdong 516100; 2. Power Generation Company Guangzhou Pumped Storage Power Station, Guangzhou 510900; 3. Machinery Industry Information Institute SIEMENS Electric Power Automation Co., Ltd, Nanjing 211100 |
|
|
Abstract This paper introduces the principleof Siemens 100% stator ground fault protection with 20Hz voltage injection, meanwhile, it also gives the cause of low voltage on the secondary side of earthing transformer, the influence on protection sensitivity, as well as the improvement measure of raising voltage, the debugging method after improvement measure. In addition, the paper also analyzes the setting method of earth current angle compensation and transmission resistance when debugging.
|
Published: 19 April 2017
|
|
|
|
Cite this article: |
Chen Fenghua,Wu Hao,Gao Dijun. The Cause and Solution of Low Watching Voltage of Siemens 100% Stator Ground Fault Protection with 20Hz Voltage Injection[J]. Electrical Engineering, 2017, 18(4): 136-139.
|
|
|
|
URL: |
http://dqjs.cesmedia.cn/EN/Y2017/V18/I4/136
|
[1] 贺儒飞. 外加电源方式100%定子接地保护的拒动与误动问题[J]. 四川电力技术, 2005, 28(1): 29-31. [2] 王维俭. 电气主设备继电保护原理与应用[M]. 北京:中国电力出版社, 1996. [3] 20Hz SEF 100% Solution_20Hz定子100%接地故障处理方案[Z]. 西门子电力自动化有限公司, 2009 [4] 伍利, 彭金宁, 姚李孝, 等. 大型发电机组注入式定子接地保护调试与整定[J]. 中国电力, 2013, 46(9): 92-95, 106. [5] 宋建军, 高迪军. 西门子20Hz电压注入式100%定子接地保护原理及调试[J]. 电力科学与工程, 2011, 27(8): 38-41. |
|
|
|