The resaon analysis and precautions of blackout in 220kV substation |
Feng Shun, Jiao Hailong |
State Gird Henan Electric Power Conporation Maintenance Company Operation, Zhengzhou 450000 |
|
|
Abstract The paper analyzes an accident of the blackout in 220kV substation. The isolated switch auxiliary contact switch is not in place, resulting in voltage switching is not normal, eventually leading to the voltage air switch tripping. At the same time, the substation occurs the accident of the blackout because of the logic defects of automatic bus transfer equipment after the PT protection voltage anomaly disappeared. This paper introduces the regulation requirements of State Grid Corporation on voltage switching circuit, and puts forward the preventive measures to optimize the logic of theautomatic bus changeover device. This paper hope these measures can provide a reference for the operation and maintenance of 220kV substation.
|
Received: 13 July 2017
Published: 22 January 2018
|
|
|
|
[1] 胡泰, 林彩健. 一起220kV变电站全站失压事故分析及预防措施[J]. 电力系统保护与控制, 2008, 36(24): 107-109. [2] 冯顺, 段乐浩, 曲欣, 等. 直流两段母线正负串电后母线对地电压的分析[J]. 电工技术, 2017(3): 15-16. [3] 江苏省电力公司. 电力系统继电保护原理与实用技术[M]. 北京: 中国电力出版社, 2006. [4] 冯顺, 曲欣, 王毅, 等. 浅析500kV智能变电站三跳失灵回路的设计[J]. 电气技术, 2017, 18(6): 120-122, 127. [5] 冯顺, 曲欣, 王毅, 等. 某变电站500kV母线保护TA断线保护闭锁分析[J]. 电气技术, 2017, 18(7): 113-116. |
|
|
|