| Hybrid energy storage combining lithium batteries and supercapacitors for automatic generation control frequency regulation technology |
| HUANG Tiangang1, LI Gang2, JIANG Nan2, MIN Xiangbin2, LI Xiaobing1 |
1. Siyuan Qingneng Electrical and Electronic Co., Ltd, Shanghai 200200; 2. Yimin Power Plant of Huaneng Yimin Coal and Electricity Co., Ltd, Hulunbuir, Inner Mongolia 021100 |
|
|
|
|
Abstract The participation of thermal power units in automatic generation control (AGC) frequency regulation is fundamental to maintaining the frequency safety of the power grid and requires assessment. Currently, thermal power units have a relatively high rate of AGC frequency regulation non-compliance, facing severe assessment pressure. In response to this issue, research on the joint participation of thermal power units and energy storage in AGC frequency regulation is conducted, and a joint frequency regulation control strategy is designed to ensure that the operation of thermal power units meets the assessment requirements. This paper, in combination with the Two Detailed Rules issued by the regional regulatory bureaus of the National Energy Administration, introduces the characteristics of hybrid energy storage and analyzes the essence of the assessment requirements for AGC frequency regulation of thermal power units. With the goal of meeting the assessment requirements, a joint AGC frequency regulation scheme and a control strategy for thermal power units equipped with fast-response energy storage are proposed, besides, the response and coordination mode between hybrid energy storage and lithium batteries is discussed. The case study shows that by implementing this control strategy, the comprehensive performance index of AGC frequency regulation of thermal power units can be significantly improved. Besides, the response and coordination methods between different hybrid energy storage and lithium batteries lead to different service lives of each.
|
|
Received: 18 June 2025
|
|
|
|
| Cite this article: |
|
HUANG Tiangang,LI Gang,JIANG Nan等. Hybrid energy storage combining lithium batteries and supercapacitors for automatic generation control frequency regulation technology[J]. Electrical Engineering, 2026, 27(3): 63-69.
|
|
|
|
| URL: |
|
https://dqjs.cesmedia.cn/EN/Y2026/V27/I3/63
|
[1] 我国光伏发电装机突破10亿千瓦火电装机占比降至约40%[EB/OL]. (2025-06-24) [2025-10-23]. https://www.gov.cn/lianbo/bumen/202506/content_7029140.htm. [2] 孙华东, 汤涌, 马世英. 电力系统稳定的定义与分类述评[J]. 电网技术, 2006, 30(17): 31-35. [3] 朱振山, 翁凯亮, 欧阳海涛. 基于动态参与因子和自适应模型预测控制的电池储能二次调频控制策略[J]. 电工技术学报, 2026, 41(1): 343-358. [4] 于仲安, 马静瑶. 含风电耦合制氢的主从博弈多区域综合能源系统协调调度策略[J]. 电气技术, 2023, 24(7): 1-10. [5] 郑冉, 夏彦辉, 赵学茂, 等. 基于云-边-端协同控制的综合型虚拟电厂[J]. 电气技术, 2023, 24(9): 40-48. [6] 李政, 刘宏伟, 康健, 等. 混合储能参与自动发电控制容量优化配置[J]. 电气技术, 2021, 22(9): 34-40. [7] 沈迎, 黄策, 胡锡东, 等. 锂离子电容器参与火电机组调频研究[J]. 电气技术, 2021, 22(10): 98-103. [8] 黄策, 燕云飞, 沈迎, 等. 超容储能辅助火电机组调频的电气问题研究[J]. 电气技术, 2022, 23(8): 103-108. [9] 胡斌, 杨中平, 黄先进, 等. 用于超级电容储能系统的三电平双向直流变换器及其控制[J]. 电工技术学报, 2015, 30(8): 83-89. [10] 张纯江, 董杰, 刘君, 等. 蓄电池与超级电容混合储能系统的控制策略[J]. 电工技术学报, 2014, 29(4): 334-340. [11] 肖云鹏, 张兰, 张轩, 等. 包含独立储能的现货电能量与调频辅助服务市场出清协调机制[J]. 中国电机工程学报, 2020, 40(增刊1): 167-180. [12] Guo Yonghong, Xie Xiaorong, Wang Bin, et al.Improving AGC performance of a coal-fueled generators with MW-level BESS[C]//2016 IEEE Power & Energy Society Innovative Smart Grid Technologies Con- ference (ISGT), Minneapolis, MN, USA, 2016: 1-5. [13] 赵源筱, 耿光超, 江全元, 等. 考虑功率变化速率的储能辅助单机调频控制策略[J]. 电力自动化设备, 2020, 40(1): 141-147. [14] 孙冰莹, 刘宗歧, 杨水丽, 等. 补偿度实时优化的储能-火电联合AGC策略[J]. 电网技术, 2018, 42(2): 426-436. [15] 李翠萍, 司文博, 李军徽, 等. 基于集合经验模态分解和多目标遗传算法的火-多储系统调频功率双层优化[J]. 电工技术学报, 2024, 39(7): 2017-2032. [16] 国家能源局南方监管局. 关于印发南方区域“两个细则”(2017版)的通知[Z]. 广州, 2017. [17] 国家能源局东北监管局. 关于印发《东北区域电力并网运行管理实施细则》《东北区域电力辅助服务管理实施细则》的通知[Z]. 沈阳, 2024. |
|
|
|