Design and Study on Application of On-line Ultrahigh Frequency Partial Discharge Detection in 1000kV GIS
Tang Huizeng1, Chen Fuan2, Luo Yahao3, Guan Shifeng1, Wei Haihao3
1. State Grid He’nan Electric Power Corporation Maintenance Company, Zhengzhou 450052;; 2. He’nan University of Technology, Zhengzhou 450007; 3. XJ Group Corporation, Xuchang, He’nan 461000
Abstract:This paper presents a overall design scheme of the UHF (Ultrahigh Frequency) partial discharge on-line detection method in 1000kV GIS (Gas Insulated Switchgear). The high frequency discharge signal is processed by the signal conditioning circuit, then the information is sent to the information acquisition and processing unit with the TMS320 microcontroller as the control core, and the final results are displayed by the upper computer software. Using the system to simulate the four kinds of insulation defects, the characteristics of the high frequency detection method are obtained. The system successfully found a GIS 1000kV basin insulator fault, the practical application effect is good.
[1] 邱毓昌. GIS装置及其绝缘技术[M]. 北京: 水利电力出版社, 1994. [2] 刘振亚. 特高压电网[M]. 北京: 中国经济出版社, 2005. [3] 周广, 刘勇. 1000kV HGIS在线特高频技术局放监测的应用[J]. 华中电力, 2011, 5(24): 57-62. [4] Lundgaard, L E, Tangen G, et al. Acoustic diagnosis of GIS; Field experience and development of expert system[J]. IEEE Trans. on Power Delivery, 7(1): 287- 293. [5] 丁登伟, 唐诚, 高文胜, 等. GIS中典型局部放电的频谱特征及传播特性[J]. 高电压技术, 2014, 40(10): 3243-3251. [6] Hasegawa Y, Izumi K, Kobayshi A, et al. Investigation on phenomena caused by insulation abnormalities in actual GIS[J]. IEEE Transactions on Power Delivery [7] 孙曙光, 陆俭国, 俞慧忠, 等. 基于UHF法的GIS局部放电测量与分析[J]. 电测与仪表, 2012, 49(4): 5-9.