The Test Analysis for Capacitor Voltage Transformer Damper Component Fault
Zhang Zhidong1, Liu Jianyue2, Li Xiuguang3, Zhang Hai4
1. Maintenance Company of Shanxi Province Electrical Power Company, Taiyuan 030021; 2. Skill Training Center of Shanxi Province Electrical Power Company, Taiyuan 030024; 3. State Grid Ningxia Electric Power Research Institute, Yinchuan 750001; 4. Shanxi Province Electrical Power Company, Taiyuan 030001
Abstract:In view of abnormality of secondary voltage in capacitor voltage transformer (CVT), based on characteristics and design parameters of the device structure, combined with the maintenance field conditions, a test method for damper component fault detection was proposed in this paper through high voltage test and circuit calculate. By analyzing examples of a fault case, describing the field test, data analysis and comprehensive judgment, it’s verify the accuracy of the method by disintegration. At the same time, the necessity of damping current detection for CVT was proposed in this paper.