摘要 电力系统中的10kV补偿电容器组断路器分合次数过多,故障层出不穷。由于10kV补偿电容器组断路器非全相分闸故障十分复杂,目前还无法对其进行有效判断。鉴于此,本文研制一种10kV补偿电容器组断路器非全相分闸监测系统,通过对该类型断路器三相均分闸、一相未分闸、两相未分闸、三相均合闸时的电容器组母线电压、三相中任一相电流及中性点电流的逻辑值进行分析,根据接入逻辑电路的带电显示器提示灯显示情况来判断断路器非全相分闸的类型。在110kV延年站51C电容器组断路器试运行时验证了该监测系统有效可行,可帮助工作人员根据带电显示器显示情况更快速地确定断路器分闸类型并采取相应措施排除故障,避免因在设备缺陷时采取不正确操作方法造成事故,保证电力系统安全运行。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
张均蔚
关键词 10kV补偿电容器断路器监测非全相分闸    
Abstract:The circuit breakers of 10kV compensation capacitor banks have too many times of opening and closing, and faults emerge in endlessly. Due to the complexity of the open phase opening fault of 10kV compensation capacitor bank circuit breaker, it is still impossible to effectively judge it. In view of this, this paper develops a 10kV compensation capacitor bank circuit breaker non-full-phase opening monitoring system. By analyzing the logic values of capacitor bank bus voltage, any phase current and neutral point current when this type of circuit breaker is three-phase equally open, one phase is not open, two phases are not open, and three phases are closed, the type of non-full-phase opening of the circuit breaker is judged according to the display of the live display indicator connected to the logic circuit. During the trial operation of 51C capacitor bank circuit breaker in 110kV Yannian Station, the monitoring system is verified to be effective and feasible, which can help staff determine the opening type of the circuit breaker more quickly according to the live display and take corresponding measures to eliminate faults, thus avoiding accidents caused by incorrect operation methods when equipment defects occur and ensuring the safe operation of the power system.
Key words10kV compensating capacitor    circuit breaker    monitoring    non-full-phase breaking   
收稿日期: 2022-10-08     
作者简介: 张均蔚(1989—),女,广东省佛山市人,硕士,工程师,主要从事变电管理工作。
引用本文:   
张均蔚. 一种10kV补偿电容器组断路器非全相分闸监测系统[J]. 电气技术, 2022, 23(12): 75-80. ZHANG Junwei. A monitoring system for non-full-phase breaking of 10kV compensating capacitor bank circuit breakers. Electrical Engineering, 2022, 23(12): 75-80.
链接本文:  
https://dqjs.cesmedia.cn/CN/Y2022/V23/I12/75