电气技术  2017, Vol. 18 Issue (10): 127-130    DOI:
技术与应用 |
一起110kV断路器操作箱防跳异常问题的探讨
吕梦丽
广东电网公司阳江供电局,广东 阳江 529500
Analysis the Abnormal Phenomenon on 110kV Breaker Anti-bouncing Circuit of Microcomputer Protection
Lv Mengli
Yangjiang Power Supply Bureau of Guangdong Power Grid Corporation, Yangjiang, Guangdong 529500
全文: PDF (308 KB)   HTML (1 KB) 
输出: BibTeX | EndNote (RIS)      
摘要 某110kV断路器保护装置在试验工作中,当测试操作箱防跳跃回路的功能时,发现断路器在合上位置,且重合闸出口压板投入时,通过测控屏上的合闸把手保持合闸指令,然后发出跳闸指令,断路器跳闸后会再次合闸,而防跳保护没有实现防跳功能。分析得知,主要是因为同期手合时合闸指令的返回时间比重合闸返回时间快造成的。本文提出并进行了针对此类操作箱防跳跃回路正确试验,且分别在不同厂家装置上进行试验,证明防跳保护可靠,实现了防跳跃功能。这对保护测控装置定检、验收和防跳跃回路故障排查等均具有一定的参考作用和指导意义。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
吕梦丽
关键词 断路器防跳跃操作箱检同期合闸回路    
Abstract:In one periodic test on the anti-bouncing circuit of 110kV circuit breaker protection and monitoring device, we found if we sent a tripping order after switching on circuit breaker and keeping switching dictation by the switching handle on measurement a control panel, circuit breaker didn't switch after tripping, but circuit breaker will switch again after tripping if the outlet pressure plate of auto-reclosure was adopted. The anti-bouncing circuit implemented actually. It is considered due to the return time of switching dictation of synchronization was faster than that of auto-reclosure. The suggestion and test method were proposed for such an operation box anti-bouncing circuit. And it has certain reference and practical significance for scheduled check, acceptance, and troubleshooting, etc.
Key wordscircuit breaker    anti-bouncing    microcomputer protection    check the same period    switching   